The HomeWorks QSX processor 1 provides control and communication to HomeWorks system components. The Ethernet links allow communication to the HomeWorks designer software, integration with third-party systems and communication between multiple processors. HomeWorks QSX processors may be connected using either an Ethernet hub /switch or router, or by using Ethernet directly from a PC to the processor(s). Clear Connect – Type X Gateways cannot be wired directly to the Ethernet port on a HomeWorks QSX processor. See page 5 for details. All processors on a project must be connected to a single network. The HomeWorks designer software and all integration equipment must be connected to the same network as the processors. The HomeWorks QSX processor is required when using the Clear Connect – Type X Gateway for control of residential Ketra light sources.
Power – Processor (P): 24–36 V- 250 mALinks (L1/L2): 24–36 V- 2 A per link
Typical Power Consumption – 4.2 W; 8 Power Draw Units (PDUs) Test conditions: Two Ethernet links connected, both device links in use
Regulatory Approvals – cULus, NOM, CE
Environment – Indoor use only. 32 °F to 104 °F (0 °C to 40 °C), 0% to 90% humidity, non-condensing
Heat Generated – 15 BTU/hr — typical (24 BTU/hr with 2 links at 2 A each output)
Cooling Method – Passive Cooling
Power Failure Memory – System data stored in non-volatile memory. Timeclock retention for 10 years
Internal Timeclock – ±1 minute per year
Miswire Protection – All terminal block inputs are over-voltage and miswire protected against wire reversals and shorts
Low-Voltage Link Wire Type – Two pair — one pair 18 AWG (0.75 mm2), one pair 18 to 22 AWG (0.34 to 0.75 mm2) twisted shielded — IEC PELV / NEC® Class 2 cable
Low-Voltage Power Wire Type – 18 AWG (0.75 mm2)
Communications – Ethernet, RS485 (QS, RF)
Link Capacities –
HomeWorks QS Wired Device Link 99 devices/512 zones
HomeWorks QS Wired Device (MDU models) 50 devices/50 zones
HomeWorks Clear Connect – Type A Link 99 devices/100 zones
ESD Protection – Meets or exceeds the IEC 61000-4-2 standard
Surge Protection – Meets or exceeds ANSI/IEEE C62.41 standard
Mounting – Mounts in HQ-LV21, L-LV14, L-LV21, or PDx- control panel
Dimensions –
With terminal blocks: 4.25 in (108 mm) x 3.94 in (100 mm)
Without terminal blocks: 4.25 in (108 mm) x 3.54 in (90 mm)
Connections –
4-pin removable terminal blocks. 1 for HQP7-1, 2 for HQP7-2.
One 4-pin removable terminal block* for Power Input.
Two RJ45 standard Ethernet connections.